The electronic pdf versions of the documents found through http://www.dnv.com/ are the officially binding versions. Copyright Det Norske Veritas.

[Book] [Expand] [Collapse] [Search Forms] [Previous Section with Hits] [Next Section with Hits] [Clear Search] [Help]

Expand Search


Sec.4: Hazardous Area Classification [Table of Contents] Sec.6: Escape and Communication

DNV-OS-A101 Safety Principles and Arrangements

[-] Sec.5: Emergency Shutdown (ESD) Principles

SECTION 5
Emergency Shutdown (ESD) Principles

Sec.5
A. General Requirements

Sec.5
A 100   Objectives

Sec.5 A
101
   The provisions of this section aim to ensure that shutdown systems are provided as suitable and effective to safeguard personnel and plant against hazardous events on the unit or installation.

Sec.5
A 200   Application

Sec.5 A
201
   These requirements shall be applied to all offshore units or installations having direct operational contact with hydrocarbons.

Sec.5 A
202
   The requirements of DNV-OS-D202 apply to the emergency shutdown system.

Sec.5
A 300   Definition

Sec.5 A
301
   An emergency shutdown system comprises:
manual input devices (push buttons)
interfaces towards other safety systems, as e.g.:
fire detection system
gas detection system
alarm and communication systems
process shutdown system
drilling and well control system
fire fighting systems
ventilation systems
a central control unit receiving and evaluating signals from the manual input devices and the interfaced systems, and creating output signals to devices that shall be shut down or activated. The ESD central shall include a device providing visual indication of initiated inputs and activated outputs and a local audible alarm
output actuators as e.g. relays, valves and dampers, including status indicators
signal transfer lines between the ESD central and all input devices, interfaced systems and output actuators
power supply.

Sec.5
A 400   Basic provisions

Sec.5 A
401
   The ESD system shall be designed so that the risk of unintentional shutdown caused by malfunction or inadvertent operation is minimised.

Sec.5 A
402
   The ESD system shall be designed to allow testing without interrupting other systems onboard.

Sec.5 A
403
   The ESD system shall have continuous availability R0 as defined in DNV-OS-D202, Ch.2 Sec.1 B200.

Sec.5 A
404
   The ESD Operator Station shall be located in a non-hazardous and continuously manned area.

Sec.5 A
405
   The ESD central control unit shall be powered from the main power system and from a monitored Uninterruptible Power Supply (UPS) capable of at least 30 minutes continuous operation on loss of main power. The UPS shall be powered from both the main and the emergency power system.

Sec.5
B. Safety and Shutdown Philosophy

Sec.5
B 100   General

Sec.5 B
101
   The philosophy shall comprise functional requirements for the safety systems upon detection of an abnormal condition. The fail-safe functionality for the safety systems shall be included.

Sec.5 B
102
   The philosophy document shall indicate actions to:
limit the duration and severity of the incident
protect personnel exposed to the incident
limit environmental impact
facilitate escape, muster and evacuation, as necessary.


Sec.5 B
103
   Inter-relationships and requirements for the following systems shall be addressed:
emergency shutdown system
fire and gas detection system
process shutdown system
drilling and well control systems
alarm and communication systems
active fire fighting systems
ventilation systems
energy sources and associated utilities required to drive essential and emergency functions.

Sec.5
C. Fail-Safe Functionality

Sec.5
C 100   General

Sec.5 C
101
   Upon failure of the shutdown system, all connected systems shall default to the safest condition for the unit or installation.

Sec.5 C
102
   The safest conditions for the systems onboard shall be defined. The safest conditions defined in Table C1 shall normally apply. Deviation from the requirements of Table C1 shall be justified.

Sec.5 C
Table C1 Safest conditions and corresponding output circuit configuration 
System Safest condition in case of failure to the
shutdown system 
Output circuit configuration 
Process plant including associated utilities  Shut down NE 
Drilling system Operational 1) NDE 
Fire pump drivers (start function) Operational NE 
Electrical power generation, including required auxiliary systems, for units not dependent upon active position keeping Shut down 2) NE 
Electrical power generation, including required auxiliary systems, for units dependent upon active position keeping Operational 2) NDE 
Uninterruptible power supplies for power generation,
control and safety systems 
Operational 2) NDE 
Propulsion and steering for units not dependent upon active position keeping Shut down 2) NE 
Propulsion and steering for units dependent upon active
position keeping 
Operational NDE 
Turret locking and turning systems 3)   
Utility systems which do not affect essential functions Shut down NE 
  1. See DNV-OS-E101 for further details.
  2. Some installations may have multiple operational modes; e.g. storage units intended to transport crude oil to port. In such cases, the safest conditions for each operational mode shall be identified and implemented (e.g. through facilities for by-pass of high level ESD trips during transit).
  3. A detailed study of the different failure modes shall be required for installations that depend on the ability to release or rotate turret. Effects of torque from mooring lines, friction, design limitations on fluid transfer systems and fairleads etc. will need to be addressed.
NDE = normally de-energised NE = normally energised 



Sec.5 C
103
   In the context of this section, 'circuit' is defined as any signal transfer facility, e.g. electrical, pneumatic, hydraulic, optical or acoustic.

Sec.5 C
104
   Failures to be considered for the shutdown system shall include broken connections and short circuits on input and output circuits, loss of power supply and if relevant loss of communication with other systems.

Sec.5
D. Protection Systems and Shutdown Logic

Sec.5
D 100   General

Sec.5 D
101
   Shutdown shall be executed in a pre-determined, logical manner to meet the objectives defined in Sec.5 B. Definition of the logic and required response time shall include consideration of interactions between systems and dynamic effects, e.g. for process plant.

Sec.5 D
102
   A shutdown logic shall be implemented to determine the response to different degrees of emergency or upset condition. The shutdown logic should be as simple as possible. The shutdown logic given in Fig.1 shall be applied as a basis with additional due recognition of installation specific requirements.

Sec.5 D
103
   Mobile Drilling Units

See Sec.8 for simplified alternatives applicable to mobile drilling units.

raster

Fig. 1   Outline of emergency shutdown logic


Sec.5 D
104
   Shutdown shall not result in adverse cascade effects, which depend on activation of other protection devices to maintain a plant in a safe condition. The shutdown system shall be designed to ensure that any ongoing operations can be terminated safely when a shutdown is activated.

Sec.5 D
105
   Shutdown shall not require unrealistically quick, undependable or complex intervention by the operator.

Sec.5 D
106
   Shutdown on a hierarchical level shall automatically include shutdowns on lower levels.

Sec.5 D
107
   The process protection system and shutdown logic shall be based on guidance given in API RP 14C or ISO 10418.

Sec.5 D
108
   Shutdown shall initiate alarm at the control station. The initiating device and operating status of devices affected by the shutdown action shall be indicated at the control station, (e.g. valve position, unit tripped, etc.).

Sec.5 D
109
   Gas detection shall initiate alarm in the crane cabin. Non-operational cranes shall be automatically de-energised if hydrocarbon gas is detected in the vicinity of the crane. Operational cranes shall be subject to manual isolation of uncertified electrical equipment and other ignition sources.

Sec.5 D
110
   Personnel lifts, work platforms and other man-riding equipment shall be designed to enable safe escape after an emergency shutdown, e.g. by controlled descent to an access point on a lower level.

Sec.5 D
111
   Systems which are not permanently attended during operation, and which could endanger safety if they fail, shall be provided with automatic safety control, alert and alarm systems.

Sec.5 D
112
   Plants that are protected by automatic safety systems shall have pre-alarms to alert when operating parameters are exceeding normal levels.

Sec.5 D
113
   The shutdown command shall not be automatically reset. Significant shutdown devices, (e.g. wellhead valves, riser ESD valves) shall be reset locally following recognition and reset at the main control room.

Sec.5
E. Automatic and Manual Shutdown

Sec.5
E 100   General

Sec.5 E
101
   Shutdowns shall normally be automatically initiated, however solely manually initiated actions may be provided where automatic action could be detrimental to safety, e.g. during drilling and dynamic positioning.

Sec.5 E
102
   Alarm for manual initiation shall be clear, and shall be readily identifiable at a permanently manned control station. The operator must have sufficient time to acknowledge and execute shutdown before an incident escalates. Manual activation shall be simple and quick to operate.

Sec.5 E
103
   In all shutdown systems, it shall be possible to manually activate all levels of shutdown at the main control station.

Sec.5 E
104
   Other manual shutdown buttons shall be located at strategic locations on the unit or installation. Locations indicated in Table E1 shall be applied as a basis with additional consideration given to installation-specific requirements.

Sec.5 E
Table E1 Location of push buttons for manual shutdown 
Shutdown level Location of push-button 
Abandon platform (APS) 
main and emergency control rooms
muster stations, lifeboat stations and helicopter deck
bridge connections between platforms
 
Emergency shutdown (ESD) As for APS, plus:
process control room
driller's control cabin
exits from process, drilling, wellhead, riser areas etc.
along main escape routes
 
Process shutdown (PSD) 
main control room
process control room
exits from process, drilling, wellhead, riser areas etc.
along main escape routes
 
Manually activated call point (MAC) Readily available for use in all normally manned areas 

It may be appropriate to limit the number of field installed pushbuttons for lower level trips (e.g. for PSD) in order to avoid confusion about their use. 



Sec.5 E
105
   For mobile offshore drilling units the arrangement shall as a minimum comply with IMO MODU Code Sec. 6.5.

Sec.5
F. Certification of Electrical Equipment for Use in an Emergency

Sec.5
F 100   General

Sec.5 F
101
   The following systems shall be operable after "Abandon Platform" (APS) shutdown:
emergency lighting, for half an hour at:
every embarkation station on deck and over sides
in all service and accommodation alleyways, stairways and exits, personnel lift cars, and personnel lift trunks
in the machinery spaces and main generating stations including their control positions
in all control stations and machinery control rooms
blowout preventer control
general alarm
public address
battery supplied radio-communication.


Sec.5 F
102
   Electrical equipment left operational after APS shutdown shall be certified for operation in zone 2 areas with the exceptions given in 104.

Sec.5 F
103
   Electrical equipment located in non-hazardous areas which is affected by a gas release, and left operational after gas detection shall be certified for zone 2, with the exceptions given in 104.

Sec.5 F
104
   Safety critical, uncertified electrical equipment may be left operational after ESD or gas detection affecting its area of location, provided that the ventilation to the room where the equipment is located is efficiently isolated. Typical living quarter design will meet this requirement, other enclosed spaces will be specially considered.
Sec.4: Hazardous Area Classification [Table of Contents] Sec.6: Escape and Communication