The electronic pdf versions of the documents found through http://www.dnv.com/ are the officially binding versions. Copyright Det Norske Veritas.

[Book] [Expand] [Collapse] [Search Forms] [Previous Section with Hits] [Next Section with Hits] [Clear Search] [Help]

Expand Search


Sec.1: General [Table of Contents] Sec.3: Arrangement

DNV-OS-A101 Safety Principles and Arrangements

[-] Sec.2: Design Principles and Accidental Loads

SECTION 2
Design Principles and Accidental Loads

Sec.2
A. General

Sec.2
A 100   Objective

Sec.2 A
101
   Application of these design principles is intended to establish an acceptable level of safety, whilst promoting safety improvements through experience and available technology.

Sec.2
A 200   Application

Sec.2 A
201
   The principles and requirements shall be applied throughout the project lifecycle, beginning in the concept phase, and reviewed and updated through detailed design and construction. The principles shall also be applied with respect to subsequent modifications.

Sec.2
B. Design Principles

Sec.2
B 100   Main principles

Sec.2 B
101
   The following general principles shall be applied throughout the concept and design phases of the unit or installation.

Sec.2 B
102
   The unit or installation shall be designed and constructed with sufficient integrity to withstand operational and environmental loading throughout its lifecycle.

Sec.2 B
103
   Systems and structures shall be designed with suitable functionality and survivability for prevention of, or protection from, design accident events affecting the unit or installation. Refer also DNV-RP-C204 - Design Against Accidental Loads.

Sec.2 B
104
   Effective escape, shelter and evacuation facilities shall be provided to safeguard all personnel, as far as practicable, at all times when the unit or installation is manned.

Sec.2
B 200   Additional requirements

Sec.2 B
201
   In meeting the main design principles in 100, the following requirements shall be applied:
  1. The design shall be sufficiently robust to tolerate at least one failure or operator error without resulting in a major hazard, or damage to the unit or installation.
  2. Suitable measures shall be provided to enable timely detection, control and mitigation of hazards.
  3. Escalation to plant and areas that are not affected by the initiating event shall be avoided.

Sec.2
C. Design for Accidental Loads

Sec.2
C 100   General

Sec.2 C
101
   The provisions given in C and D are based on international practice, experience with offshore designs and results obtained by various risk assessments carried out on offshore units. For relatively standardised designs (e.g. typical drilling units) the prescriptive requirements given in these standards are intended to anticipate the most likely hazards which may be encountered.

Sec.2 C
102
   Each project shall, however, consider the applicability of the generic load approach used in D with respect to the intended application and operation in order to identify, where applicable, hazards associated with non-standard design or application.

Sec.2 C
103
   For complex or non-standard applications a more comprehensive assessment shall be carried out. Guidance on carrying out such an assessment is given in Appendix B.

Sec.2
D. Generic Design Accidental Loads

Sec.2
D 100   General

Sec.2 D
101
   The prescriptive requirements given here and elsewhere in DNV offshore standards are intended to take account of accidental events which have been identified through previous risk studies and through experience.

Sec.2 D
102
   The requirements are based on consideration of the integrity of the following main safety functions:
integrity of shelter areas
usability of escape ways
usability of means of evacuation
global load bearing capacity.


Sec.2 D
103
   The selection of relevant design accidental loads is dependent on a safety philosophy considered to give a satisfactory level of safety. The generic loads defined here represent the level of safety considered acceptable by DNV, and are generally based on accidental loads affecting safety functions which have an individual frequency of occurrence in the order of 10-4 per year. This will normally correspond to an overall frequency of 5 x 10-4 per year as the impairment frequency limit.

Sec.2 D
104
   The most relevant design accidental loads are considered to be:
impact loads, including dropped object loads and collision loads
unintended flooding
loads caused by extreme weather
explosion loads
heat loads.


Sec.2 D
105
   This standard is intended to address the above design accidental loads. Other additional relevant loads that may be identified for a specific design or application will need to be separately addressed.

Sec.2
D 200   Dropped objects

Sec.2 D
201
   It is assumed that lifting arrangements comply with Sec.3 F with regard to location of cranes and lay down areas and with respect to lifting operations over pressurised equipment.

Sec.2 D
202
   It is assumed that critical areas are designed for dropped object loads as defined in 203 and 204.

Sec.2 D
203
   The weights of the dropped objects to be considered for design of the structure are normally taken as the operational hook loads in cranes.

Sec.2 D
204
   The impact energy is normally not to be less than:
raster  
mass of object (tonnes) 
g0 9.81 m/s2 
drop height in air (m) 

Sec.2
D 300   Collision loads

Sec.2 D
301
   The kinetic energy to be considered is normally not to be less than:
14 MJ (Mega Joule) for sideways collision
11 MJ for bow or stern collision

corresponding to a supply vessel of 5000 tonnes displacement with impact speed v = 2 m/s.

Sec.2 D
302
   The impact energy is given as:

raster

displacement of vessel (t) 
added mass of vessel, normally assumed as 0.4 M for sideways collision and 0.1 M for bow or stern collision 
impact speed (m/s). 



Sec.2 D
303
   It is assumed that the unit or installation is not operating in a shipping lane. In such case a more detailed assessment of relevant collision loads shall be carried out.

Sec.2 D
304
   Where a unit is operating in tandem with a shuttle tanker, special precautions shall be taken to minimise possibility of collision, or the design is to take account of collision loads.

Sec.2
D 400   Unintended flooding

Sec.2 D
401
   The design sea pressure on watertight subdivisions (bulkheads and decks with compartment flooded) shall for accidental damaged condition be taken as:

raster

hb vertical distance in m from the load point to the damaged waterline. 

Sec.2
D 500   Loads caused by extreme weather

Sec.2 D
501
   Characteristic values of individual environmental loads are defined by an annual probability of exceedance equal to
10-2 (for Ultimate limit states, ULS) and 10-4 (for Accidental limit states, ALS).

Sec.2
D 600   Explosion loads

Sec.2 D
601
   Requirements given in this standard are applicable to hydrocarbon gases. Where hydrogen, ethylene or acetylene is used in large quantities special consideration shall be given to explosion loads.

Sec.2 D
602
   In a ventilated compartment the explosion load given by the explosion overpressure and duration is mainly determined by the relative ventilation area and the level of congestion.

Sec.2 D
603
   The design overpressure in a ventilated shale shaker room with volume less than 1000 m3, with moderate congestion, may be taken as 200 kPa (2 barg), combined with a pulse duration of 0.3 s, unless a more detailed assessment is carried out.

Sec.2 D
604
   The design overpressure in connection with explosion on open drill floor area may be taken as 10 kPa (0.1 barg), combined with a pulse duration of 0.2 s, unless a more detailed assessment is carried out.

Sec.2 D
605
   Where a more detailed assessment is carried out in evaluating the explosion load in a vented compartment, the considerations given in 606 to 609 shall be accounted for.

Sec.2 D
606
   The vent area, Av, can be taken as the sum of free opening areas and blowout panel areas (i.e. light weather cladding) provided the static opening pressure of the panels is less than 5 kPa (0.05 barg). The relative vent area, a, is given as Av or Volume2/3.

Sec.2 D
607
   If panels or walls are intended to give explosion relief by failing, a maximum pressure up to 2 to 3 times their static release pressure can still be expected within the compartment.

Sec.2 D
608
   For compartments where the length to diameter ratio, L/D, is greater than 3, the long flame acceleration distance available tends to result in higher pressures. The diameter can be estimated as D = ÖA where A is the smallest cross-sectional area. L is the greatest dimension of the compartment.

Sec.2 D
609
   Where it is possible for an explosion to propagate from compartment to compartment and for tunnels and chutes where explosion venting can be foreseen at one end only, detailed investigations shall be carried out.

Sec.2 D
610
   Design explosion overpressure in a completely enclosed compartment handling hydrocarbons (e.g. STP or STL rooms) shall be subject to special attention. The following principles shall apply:
  1. Generally, bulkheads that need to remain intact after an explosion, e.g. towards storage tanks, shall be designed for an overpressure of 400 kPa (4 barg) and a pulse duration of 1 s. This assumes that the safety features required elsewhere in this standard are in place, i.e. control of ignition sources through area classification, provision of suitable ventilation, gas detection and emergency shutdown systems.
  2. If a lower explosion design pressure is used this must be justified through more detailed assessment.


Sec.2 D
611
   It is assumed that the process plant is designed with a suitable blowdown system and deluge system in accordance with a recognised code (e.g. DNV-OS-E201), in order to avoid possible pressure vessel rupture.

Sec.2 D
612
   Doors for pig launchers shall be oriented in a direction where inadvertent opening would result in minimal damage.

Sec.2 D
613
   For process areas on open deck covering a relatively small area (e.g. 20 m x 20 m) an explosion overpressure of 30 kPa (0.3 barg) may be used in design combined with pulse duration of 0.2 s.

Sec.2 D
614
   For process areas on open deck covering a medium size area (e.g. 20 m x 40 m) an explosion overpressure of 100 kPa (1.0 barg) may be used in design combined with pulse duration of 0.2 s.

Sec.2 D
615
   For process areas on open deck covering a larger footprint than in 614 an explosion overpressure of 200 kPa (2.0 barg) may be used in design combined with pulse duration of 0.2 s.

Sec.2 D
616
   Design shall as far as possible aim to minimise the possibility of gas build up.

Sec.2 D
617
   The following items shall be designed to withstand the specified design overpressure:
protective walls
structures capable of blocking escape ways
safety systems (and control lines)
structure supporting hydrocarbon containing equipment.


Sec.2 D
618
   Typical design values are summarised in Table D1. This shall be read together with the reservations in the text of D.

Sec.2 D
Table D1 Nominal Overpressures 
Area no. Offshore Installation Area 1) Design Blast
Overpressure 2)
(barg) 
Pulse
Duration
(s) 
Drilling rig Drill floor with cladded walls 0.1 0.2 
Drilling rig Shale shaker room with strong walls, medium sized 0.3 
Mono-hull FPSO Process area, small 0.3 0.2 
Mono-hull FPSO Process area, medium 3) sized with no walls or roof 4) 0.2 
Mono-hull FPSO, large Process area, large with no walls or roof 0.2 
Mono-hull FPSO Turret in hull, STP/STL room with access hatch 
Production platform, Semi-sub Process area, large with no or light walls, 3 storeys, grated mezzanine and upper decks 5) 0.2 
Production platform, fixed Process area, medium sized, solid upper and lower decks 6), 3 storeys, 1 or 2 sides open 1.5 0.2 
Integrated Prod/Drilling Process area and drilling module each medium sized on partly solid decks, 3 storeys, 3 sides open 1.5 0.2 
10 Integrated Prod/Drilling X-mas tree/wellhead area, medium sized with grated floors 0.2 
Notes:
  1. All areas, with the exception of #1 and #6, are considered to be congested. Designs intended to give an even more compact process area than typical offshore practice are expected to have larger nominal overpressures.
  2. All leak rates are considered, but for explosions, large leaks (e.g. 50 kg/s) dominate the explosion risk.
  3. The terms small, medium, large for process area are not specifically defined, however examples of typical footprint sizes are given in the text above
  4. A process area with more than one level is expected to have somewhat higher overpressure if the footprint area is the same.
  5. A design with solid mezzanine and upper decks would result in a higher nominal overpressure
  6. If all decks are grated the nominal overpressure is expected to be lower.
 

Sec.2
D 700   Heat loads

Sec.2 D
701
   Where the living quarters are exposed to a heat load below 100 kW/m2 a passive fire protection rating of A-60 is considered sufficient for the surface facing the source of the heat load. For heat loads above 100 kW/m2 H-rated protection shall be used.

Sec.2 D
702
   Where radiation levels at lifeboat stations exceeds 12.5 kW/m2, radiation protection shall be provided.

Sec.2 D
703
   Heat loads as a result of blowout during drilling operations will primarily be a function of blowout rate, hydrocarbon composition, and distance. The relationship related to impact on safety functions is shown in Figures 1 and 2.

raster

Fig. 1   Distance to impact levels as function of blowout rate.
100% methane

raster

Fig. 2   Distance to impact levels as function of blowout rate.
75% oil and 25% gas



Sec.2 D
704
   For drilling in water depths less than 100 m the potential effects of subsea blowouts must also be considered.

Sec.2 D
705
   For production units or installations, heat loads in connection with ignition following loss of containment of hydrocarbons shall be taken as follows, unless otherwise documented:
  1. In areas with both gas containing and oil or condensate containing equipment, critical items shall be designed to withstand a jet fire (250 kW/m2) for 30 minutes and a pool fire (150 kW/m2) for the following 30 minutes.
  2. In areas with only oil or condensate containing equipment, critical items shall be designed to withstand a pool fire (150 kW/m2) for 60 minutes.
  3. In areas with only gas containing equipment, critical items shall be designed to withstand a jet fire (250 kW/m2) for 30 minutes.


Sec.2 D
706
   The following critical items shall be designed to withstand the specified design heat load:
protective walls
structures supporting hydrocarbon pressure vessels
structures capable of blocking escape ways
essential safety systems
main structure.

Sec.1: General [Table of Contents] Sec.3: Arrangement